    Hello everyone, my Opensprinkler 2.3 DC (2.1.7 firmware) just reboots every time I try and start a station. The station is never shown as active in the app or web page. I tried factory reset, but nothing changed. Any suggestion? Thanks a million!

    #75217

    Ray
    Keymaster

    This is usually a sign of a solenoid problem. Such as a shorted solenoid or a shorted wire. To diagnose, remove the common (COM) wire and see if this still happens.

    #75219

    Marco83
    Participant

    Thanks a million Ray!
    The controller still reboots when starting a station even if I disconnect the solenoid wires completely.
    However, I got it 100% back into business by powering it not through the DC adapter, but through the USB connection (the one used for updating the firmware).
    I would be glad to fix it anyway, what do you suggest I should replace?

    Thanks!

    #75221

    Ray
    Keymaster

    That’s really strange. It sounds like the power adapter is failing and cannot provide enough current. You can try a different DC power adapter. Anything that outputs a DC voltage that’s between 7.5V to 12V and can provide at least 1amp current should work.

    #75262

    Marco83
    Participant

    I tried replacing the DC adapter with a new unit and everything seems to be working spotless.
    So there was never anything wrong with the Opensprinkler, only with the DC power adapter!
    Thanks for the precious help

    #75263

    Ray
    Keymaster

    Sure thing. Glad to hear it’s working again.