  • #81591

    kakas
    Participant

    If I’m correct, the firmware does not use the measured current value for anything other than displaying it. (and sending it for API request)
    Are there any plans to detect shorted circuits, when current is higher than a set value, or broken lines?

    #81598

    Ray
    Keymaster

    Correct, it’s currently for display only. You can use it to manually check if there is any broken lines, for example, if the current is too low when a zone is on, that generally indicates the solenoid is not activated.

    There is no plan yet to use the current sensor for triggering any actions, although similar to the Flow Alert, it’s fairly easy to implement a current sensor alert. Note that often when there is a shorted circuit, it would result in a tripped fuse, or the power supply voltage collapsing triggering an immediate reboot — there won’t be enough time for the current sensor to even read a reliable value.